A-B Remote I/O Adapter to IEC60870-5-101 Slave Communication Module
5601-RIO-101S
Product Description
The ProLinx family A-B Remote I/O Adapter to IEC60870-5-101 Slave communications module (5601-RIO-101S) creates a powerful connection between devices on an IEC 101 network and a Remote I/O master device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Remote I/O port and one IEC 101 Slave configurable serial port.
The RIO interface is an adapter (slave) which can be connected to a scanner (master) that controls the data transfer. The module also supports limited high speed data transfer via the Input and Output images.
The IEC 60870-5-101 Slave (101S) protocol driver supports Slave implementations of the protocol. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.
Product Applications
The RIO-101S modules are the ideal solution for the many applications where IEC 101 Slave connectivity can be used to integrate a Remote I/O master device into a system.
The IEC60870-5-101 Slave gateway is a powerful module designed with Slave support, enabling easy connection to IEC 101 master devices. In combination with the Remote I/O device support, the module provides a very powerful interface to the many Remote I/O master devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing
.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
A-B Remote I/O Adapter Specifications
The RIO interface is an adapter (slave) and is connected to a scanner (master) that controls the data transfer.
As an example, the master/slave relationship can be accomplished using the 460X-RIO-XXX module (adapter/slave unit) with an Allen-Bradley PLC5 (scanner/master unit). Ladder logic must be programmed into a PLC to perform BTR/BTW commands to receive and transmit data between the module and the PLC. The module also supports limited high speed data transfer via the Input and Output images.
|
Software Configurable Parameters
|
|
Rack Number Addressing
|
0 to 63
|
|
Rack Size
|
¼-rack, ½-rack, ¾-rack and full rack
|
|
Starting Group
|
0,2,4,6
|
|
Last Rack
|
Yes or No
|
|
Baud Rate
|
57.6K, 115K, 230K
|
|
Functional Specifications
|
|
Supports block-transfers of data with scanner
|
|
Supports I/O data movement. Amount determined by rack size configuration
|
|
BTW Command - up to 64 words
|
|
BTR Command - up to 63 words
|
|
Physical Connection
|
|
Remote I/O connector
|
Standard 3-screw termination connector.
|
IEC 60870-5-101 Slave Protocol Specifications
The 101S module acts as a gateway between the IEC-870-5-101 other protocols and networks, as well as several proprietary interfaces.
General specifications include:
- User-definable module memory usage
- Storage of IEC time used in module is available in the database
- Protocol implementation conforms to the IEC-870-5-101 specification with fully configurable parameters
- Priority Queues
- Invalid Bit Monitoring
- Supports Balanced and Unbalanced Mode
- Supports CP24 and CP56 time formats for events
- Event generation configurable per point or data type
|
General Parameters
|
|
Communication parameters
|
Baud Rate: 110 to 38,400 baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd RTS Timing Delays: 0 to 65535 ms
|
|
IEC 870-5-101 Slave
|
|
Configurable Parameters
|
Data link address length
Common Address of ASDU length
Inform. Object Address length
Select/Operate Timeout
Event Scan delay
Use Balanced Mode
Short Pulse Time
Long Pulse Time Time DB Offset
|
|
Status Data
|
Status data is returned in a block of counter values allowing communications to be effectively debugged.
|
|
Supported Data Types
|
M_SP_NA
M_DP_NA
M_ST_NA
M_ME_NA
M_ME_NB
M_ME_NC
M_IT_NA
C_SC_NA
C_DC_NA
C_RC_NA
C_SE_NA
C_SE_NB C_SE_NC
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
RIO Connector
|
3 pos screw-terminal adaptor(J803)
|
|
RIO LED Indicators
|
Active - Green
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
Ordering Information
|
5601-RIO-101S
|
A-B Remote I/O Adapter to IEC60870-5-101 Slave
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|