ProSoft Technology, Inc.
Home > Products > Stand-alone Gateways > Serial > IEC60870-5-101 Slave > A-B Remote I/O Adapter to IEC60870-5-101 Slave Communication Module
Printable Page
 

Search | Clear


A-B Remote I/O Adapter to IEC60870-5-101 Slave Communication Module

5601-RIO-101S

Product Description

The ProLinx family A-B Remote I/O Adapter to IEC60870-5-101 Slave communications module (5601-RIO-101S) creates a powerful connection between devices on an IEC 101 network and a Remote I/O master device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Remote I/O port and one IEC 101 Slave configurable serial port.

The RIO interface is an adapter (slave) which can be connected to a scanner (master) that controls the data transfer. The module also supports limited high speed data transfer via the Input and Output images.

The IEC 60870-5-101 Slave (101S) protocol driver supports Slave implementations of the protocol. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.

Product Applications

The RIO-101S modules are the ideal solution for the many applications where IEC 101 Slave connectivity can be used to integrate a Remote I/O master device into a system. The IEC60870-5-101 Slave gateway is a powerful module designed with Slave support, enabling easy connection to IEC 101 master devices. In combination with the Remote I/O device support, the module provides a very powerful interface to the many Remote I/O master devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing .

Functional Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

A-B Remote I/O Adapter Specifications

The RIO interface is an adapter (slave) and is connected to a scanner (master) that controls the data transfer.

As an example, the master/slave relationship can be accomplished using the 460X-RIO-XXX module (adapter/slave unit) with an Allen-Bradley PLC5 (scanner/master unit). Ladder logic must be programmed into a PLC to perform BTR/BTW commands to receive and transmit data between the module and the PLC. The module also supports limited high speed data transfer via the Input and Output images.

Software Configurable Parameters

Rack Number Addressing

0 to 63

Rack Size

¼-rack, ½-rack, ¾-rack and full rack

Starting Group

0,2,4,6

Last Rack

Yes or No

Baud Rate

57.6K, 115K, 230K

Functional Specifications

Supports block-transfers of data with scanner

Supports I/O data movement. Amount determined by rack size configuration

BTW Command - up to 64 words

BTR Command - up to 63 words

Physical Connection

Remote I/O connector

Standard 3-screw termination connector.

IEC 60870-5-101 Slave Protocol Specifications

The 101S module acts as a gateway between the IEC-870-5-101 other protocols and networks, as well as several proprietary interfaces.

General specifications include:

  • User-definable module memory usage
  • Storage of IEC time used in module is available in the database
  • Protocol implementation conforms to the IEC-870-5-101 specification with fully configurable parameters
  • Priority Queues
  • Invalid Bit Monitoring
  • Supports Balanced and Unbalanced Mode
  • Supports CP24 and CP56 time formats for events
  • Event generation configurable per point or data type

General Parameters

Communication parameters

Baud Rate: 110 to 38,400 baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd
RTS Timing Delays: 0 to 65535 ms

IEC 870-5-101 Slave

Configurable Parameters

Data link address length
Common Address of ASDU length
Inform. Object Address length
Select/Operate Timeout
Event Scan delay
Use Balanced Mode
Short Pulse Time
Long Pulse Time
Time DB Offset

Status Data

Status data is returned in a block of counter values allowing communications to be effectively debugged.

Supported Data Types

M_SP_NA
M_DP_NA
M_ST_NA
M_ME_NA
M_ME_NB
M_ME_NC
M_IT_NA
C_SC_NA
C_DC_NA
C_RC_NA
C_SE_NA
C_SE_NB
C_SE_NC

Hardware Specifications

Power Supply 24 VDC nominal
  18-32 VDC allowed
  Positive, Negative, GND Terminals
  2.5 mm screwdriver blade

Current Load

500 mA max@ 32 VDC max
Operating Temperature -20 to 50 Deg C
  -4 to 122 Deg F
Storage Temperature -40 to 85 Deg C
  -40 to 185 Deg F
Relative Humidity 5-95% (w/o condensation)
Dimensions

Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD

LED Indicators

Power and Module Status

  Application Status
  Serial Port Activity LED
  Serial Activity and Error LED Status
Configuration Serial Port Mini-DIN
  RS-232 only
  No hardware handshaking
Ethernet Port 10Base-T Connector
  Link and Activity LED indicators
  Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
  Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Application Serial Ports Mini-DIN
  RS-232/422/485
  RS232 handshaking configurable
  RS422/485 screw termination included
Port Isolation 2500V Opto-Isolators
  500V Power Supply Isolation
Shipped with each unit Mini-DIN to DB-9M cables per serial port
  4 ft RS-232 configuration cable
  2.5mm screwdriver
  CD (docs and Configuration utility)
  RS-422/485 DB9 to Screw Terminal
  Adaptor (1 or 4, depending on ports)

RIO Connector

3 pos screw-terminal adaptor(J803)

RIO LED Indicators

Active - Green

Click here for dimensions diagram

Certifications

The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2


Ordering Information

5601-RIO-101S

A-B Remote I/O Adapter to IEC60870-5-101 Slave

To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

Image Gallery