A-B Remote I/O Adapter to DF1 Master/Slave Communication Module
5601-RIO-DFCM
5602-RIO-DFCM4
Product Description
The ProLinx family A-B Remote I/O Adapter to DF1 Master/Slave communications module creates a powerful connection between devices on a Remote I/O network and DF1 devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Remote I/O port and up to four serial ports.
The RIO interface is an adapter (slave) which can be connected to a scanner (master) that controls the data transfer. The module also supports limited high speed data transfer via the Input and Output images.
The DF1 (DFCM) protocol driver supports Master or Slave implementations of the protocol on each DF1 port. All DF1 ports are individually configurable, providing a great deal of flexibility.
Product Applications
The RIO-DFCM modules are the ideal solution for the many applications where Remote I/O connectivity can be used to integrate DF1 Master/Slave devices into a system.
The Remote I/O gateway is a powerful module designed with both Client and Server support, enabling easy connection to Rockwell Automation PLCs (CLX, SLC, PLC, CPLX, and similar devices). In combination with the DF1 device support, the module provides a very powerful interface to the many DF1 devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing
.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
A-B Remote I/O Adapter Specifications
The RIO interface is an adapter (slave) and is connected to a scanner (master) that controls the data transfer.
As an example, the master/slave relationship can be accomplished using the 460X-RIO-XXX module (adapter/slave unit) with an Allen-Bradley PLC5 (scanner/master unit). Ladder logic must be programmed into a PLC to perform BTR/BTW commands to receive and transmit data between the module and the PLC. The module also supports limited high speed data transfer via the Input and Output images.
|
Software Configurable Parameters
|
|
Rack Number Addressing
|
0 to 63
|
|
Rack Size
|
¼-rack, ½-rack, ¾-rack and full rack
|
|
Starting Group
|
0,2,4,6
|
|
Last Rack
|
Yes or No
|
|
Baud Rate
|
57.6K, 115K, 230K
|
|
Functional Specifications
|
|
Supports block-transfers of data with scanner
|
|
Supports I/O data movement. Amount determined by rack size configuration
|
|
BTW Command - up to 64 words
|
|
BTR Command - up to 63 words
|
|
Physical Connection
|
|
Remote I/O connector
|
Standard 3-screw termination connector.
|
DF1 Master/Slave Protocol Specifications
The DF1 Master/Slave Protocol driver provides extensive support for both Master and Slave implementations of the protocol. The serial port on the gateway is user-configurable to support the DF1 protocol (Master or Slave, Error Checking, Baud rate, etc).
|
General Parameters (Software Configurable)
|
|
Type
|
Specifications
|
|
Communication parameters
|
Local Station ID: 0 to 254
Baud Rate:110 to 115K baud
Stop Bits: 1
Data Size: 8 bits
Parity:None, Even, Odd RTS Timing delays:0 to 65535 ms
|
|
Error Checking
|
BCC and CRC
|
|
Miscellaneous
|
- Full hardware handshaking control, providing radio, smart modem and multi-drop support
- Floating point data supported
|
DF1 Master Protocol Specifications
The ports on the module can be individually configured as Master ports. When configured in master mode, the DFCM module is capable of reading and writing data to remote DF1 devices.
The DF1 Master functionality supported by the module includes:
|
DF1 Master Driver
|
|
Type
|
Specifications
|
|
DF1 Modes
|
Full-Duplex - Master (Module generates commands) Half-Duplex - Polling
|
|
DF1 Supported Commands
|
Basic Command Set
0x00 Protected Write
0x01 Unprotected Read
0x02 Protected Bit Write
0x05 Unprotected Bit Write 0x08 Unprotected Write
PLC-5 Command Set (0x0F)
0x00 WordRange Write (Binary Address)
0x01 WordRange Read (Binary Address)
0x26 Read-Modify-Write (Binary Address)
0x00 WordRange Write (ASCII Address)
0x01 WordRange Read (ASCII Address) 0x26 Read-Modify-Write (ASCII Address)
SLC Command Set (0x0F)
0xA1 Prot Typed Read w/2 addr fields
0xA2 Prot Typed Read w/3 addr fields
0xA9 Prot Typed Write w/2 addr fields
0xAA Prot Typed Write w/3 addr fields 0xAB Prot Typed Write w/Mask 3 addr fields
|
|
Command List
|
Up to 100 commands per Master port, each fully-configurable for function, slave address, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes available on an individual command basis. In addition, a slave status list is maintained per active master port.
|
|
Polling of Command List
|
User-configurable polling of commands, including disabled, continuous, and on change of data (write only)
|
DF1 Slave Protocol Specifications
The ports on the module can be individually configured to support the slave mode of the DF1 protocol. When in slave mode, the module can accept DF1 commands from a master to read/write data stored in the module's internal registers.
The DF1 Slave functionality supported by the module includes:
|
DF1 Slave Driver
|
|
Type
|
Specifications
|
|
DF1 Modes
|
Full Duplex - Slave (not peer mode) Half Duplex - Polled
|
|
Configurable parameters per slave port
|
Data Table File Start (File N[x] 0 to 999)
Data Table File Size (1 - 1000 words) Data Table location in database (0 to 3999)
|
|
DF1 Supported Commands
|
Basic Command Set
0x00 Protected Write
0x01 Unprotected Read
0x02 Protected Bit Write
0x05 Unprotected Bit Write 0x08 Unprotected Write
PLC-5 Command Set (0x0F)
0x00 WordRange Write (Binary Address)
0x01 WordRange Read (Binary Address)
0x00 WordRange Write (ASCII Address) 0x01 WordRange Read (ASCII Address)
SLC Command Set (0x0F)
0xA1 Prot Typed Read w/2 addr fields
0xA2 Prot Typed Read w/3 addr fields
0xA9 Prot Typed Write w/2 addr fields 0xAA Prot Typed Write w/3 addr fields
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
RIO Connector
|
3 pos screw-terminal adaptor(J803)
|
|
RIO LED Indicators
|
Active - Green
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
Ordering Information
|
5601-RIO-DFCM
|
A-B Remote I/O Adapter to DF1 Master/Slave
|
|
5602-RIO-DFCM4
|
A-B Remote I/O Adapter to DF1 Master/Slave 4 port
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.