DeviceNet Scanner/Slave Network Interface for Quantum

PTQ-DNET

The DeviceNet Scanner/Slave Network Interface for Quantum is an interface between DeviceNet slave devices and a Schneider Electric Quantum platform processor.

DeviceNet is a low-level network that provides connections between simple industrial devices (sensors, actuators) and higher-level devices (controllers). DeviceNet is based on the Common Industrial Protocol (CIP) and shares all the common aspects of CIP with adaptations to fit the message frame size of DeviceNet.

The DeviceNet Scanner/Slave Network Interface supports complete specifications according to CAN bus and ISO 11898 standards and the Common Industrial Protocol (CIP) for the upper layers of their network protocol.

Features and Benefits

  • Allows connection for a single DeviceNet network
  • Connect up to 63 slave devices
  • Supports either Scanner or Slave modes
  • Supports Auto Device Replacement (ADR); consists of Node Recovery and Configuration Recovery
    • Node Recovery - node number must be writable over the DeviceNet network and must initially be set to 63
    • Configuration Recovery - this feature causes the replacement device's configuration to be made identical to the original device. The replacement device's configuration must be writable over the DeviceNet network. Configuration Recovery files are stored in the master scanner that is communicating with the original device through RSNetWorx for DeviceNet
  • Provides processor module status and access to scanner network diagnostic tables such as node idle, node status, and node fault information
  • Acts as an I/O data server for explicit peer-to-peer messaging
  • DeviceNet bandwidth can be saved by not transferring I/O values unless a change-of-state (COS) has occurred
  • DeviceNet transfer of I/O data can be scheduled (cyclic data)

Applications

The DeviceNet network is based on the producer consumer network model allowing for real-time control data exchange, configuration capabilities exclusive from control performance, and collection of data at regular intervals or based on-demand. Industries using DeviceNet:

  • Water/Wastewater
  • Factory Automation applications
  • Automotive
  • Food Processing/packaging
  • Conveyors
  • Other high speed applications

Functional Specifications

Module has been tested and certified according to ODVA guidelines to guarantee proper interoperability on a DeviceNet network.

  • DeviceNet Data:
    • Strobe, poll, COS, or cyclic I/O data
    • Configurable data parameters include: Complete data mapping between PLC scan and I/O image tables and DeviceNet devices
    • Background poll rate
    • Strobe or poll for each node
  • PLC Processor-to-Scanner Communication
    • o Synchronous Transfer: 973 Input Words and 990 Output words, plus status and control data
  • Easy-to-use drag and drop configuration view via DeviceNet Configuration Software PSW-DNET (requires USB-to-DeviceNet adapter, available separately)
  • Unity Pro and Concept Function Blocks provided
  • Electronic Keying allows the scanner to match device by device type, vendor, product code and major revision for I/O exchange
  • Embedded EDS - allows the EDS to be retrieved directly from the module
  • Slave Mode - allows the scanner to act as a slave to another scanner
  • Auto Scan - enables the scanner to automatically generate a scan list of devices on the network
  • Supports CIP Explicit Messaging via PLC ladder logic
  • Quantum 140 CPU 311 10 not supported

Additional Products

PTQ-DFNT

EtherNet/IP Client/Server Communication Module.

PSW-RSNetWorx-DNET (required)

RSNetWorx for DeviceNet Configuration Software (Rockwell Automation part number 9357-DNETL3)

The PTQ-DNET DeviceNet module set in scanner mode requires configuration software not included with the module but available from ProSoft Technology. Please see part number PSW-RSNetWorx-DNET for additional information.

Hardware Specifications

Specification

Value

Power Consumption

DeviceNet Current Load: 50 mA (max.)

Backplane Current Load: 0.8A @ 5 VDC max.

Communication Rates

125 Kbits/s, 250 Kbits/s, 500 Kbits/s

Messaging Capabilities

Master: Poll, strobe, COS, or cyclic

Explicit: Initiate and respond

Isolation

Optical isolation between:

Backplane and Channel 1

1 MW resistor from Channel 1 to chassis

Immunity Radiated Fields

10 V/m, 27 to 1000 MHz

Module Location

Quantum local I/O chassis

Network Address

00 to 63

Operating Temperature

0 to 60° C (32 to 140° F)

Storage Temperature

-40 to 85° C (-40 to 185° F)

Relative Humidity

5 to 95% (non-condensing)

Vibration

Sine vibration 4 to 100 Hz in each of the three orthogonal axes

Shock

30G, 11 mSec. in each of the three orthogonal axes

Dimensions (HxWxD), Approx.

250 x 103.85 x 40.34 mm

9.84 x 4.09 x 1.59 in

Weight

0.9 kg (1.9 lb)

Certifications

UL, CE, C-Tick, CSA Class I Div 2 Hazardous

Ordering Information

PTQ-DNET DeviceNet Scanner/Slave Network Interface for Quantum
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa